亚洲精品无码不卡av_麻豆国产尤物av尤物在线看_国产天美传媒一卡二卡_久久免费只有精品国产_亚洲日韩欧洲乱码av夜夜摸_日韩av成人片在线观看免费_久久99久久99精品歐美_无码人妻aⅴ一区二区三区a片简_国产综合人妻在线欧美日韩_久久大香萑太香蕉av黄软件

86 536 6132678
Home/Products/Rail transit equipment/Energy-saving auto-transformers

Energy-saving auto-transformers

The product has the characteristics of compact structure, low loss, low noise, energy conservation and environmental protection. Reduced the empty load loss of the product, improved capacity utilization, and achieved significant energy-saving effects.

Home/Products/Rail transit equipment/Energy-saving auto-transformers

Product Description

In response to the demand of China Railway Corporation for energy-saving products, the company has developed a new type of energy-saving autotransformer. This product has passed various test indicators of the National Transformer Inspection and Testing Center in one go: the no-load loss of the same capacity autotransformer has decreased by 28.5% and the load loss has decreased by 23.4% compared to the current operation. It has been determined as the first energy-saving product (set) in China and the first set of technical equipment in Shandong Province, and has passed the national new product appraisal. The appraisal committee unanimously believes that the overall technical indicators of this product have reached the forefront level and can be promoted for use. The product has now been connected to the grid for power transmission at the Jiaogezhuang AT station and the Pingdu North section station of the Weilai high-speed railway.


Product features

The product has the characteristics of compact structure, low loss, low noise, energy conservation and environmental protection.

1. Reduced the empty load loss of the product, improved capacity utilization, and achieved significant energy-saving effects.

2. Adopting advanced technology, the oil flow speed is accelerated, the heat dissipation efficiency is improved, the temperature rise is effectively reduced, and the overload capacity is improved.

3. Improved short-circuit resistance, reduced short-circuit impedance, greatly increased terminal voltage of the line, reduced and mitigated the impact of short-circuit point power, and ensured the operation of the transformer.


Technical Parameter

Transformer capacity(KVA)High pressure(kV)Low pressure(kV)Connection symbolNo-load loss(kW)Load loss(kW)No-load current(%)
63002x27.527.5Ia02.7712.640.45
80003.2115.210.40
100003.6517.940.40
126004.3821.220.35
160005.2625.740.35
200006.2129.640.35
250007.3135.10.25
320008.7642.120.25
4000010.2249.920.25
  • Previous:Remote control box-type substations for railways
  • Next: Energy-saving high-speed rail traction transformers